{"requirement_id":"JDDG25-14.11.8.3-R05","source":{"document":"Japan District Design Guide","version":"9.0","publication_date":"2025-04","chapter":"14","section":"14.11.8.3","title":"NEUTRAL SIZING","page_printed":262,"page_pdf":292,"fact":"For data-processing applications, the neutral is to be sized at a minimum of 200 percent of phase conductors unless harmonic analysis or field data supports a smaller size.","modality":"imperative","strength":"conditional_mandatory"},"localization_ja":{"language":"ja","title_ja":"中性線サイズ選定","title_status":"controlled_editorial","fact_ja":null,"fact_translation_status":"pending","modality_rendering_ja":"条件を満たす場合は～すること","strength_label_ja":"条件付き必須","translation_priority":"high","translation_notes":[],"title_translation_provenance":"editorial_controlled","fact_translation_provenance":"not_translated","publication_eligible":false},"references":[],"meaning":{"engineering_basis":null,"engineering_basis_source":null,"engineering_interpretation":null,"interpretation_confidence":null},"risk":{"failure_modes":[],"failure_mode_source":"not_stated","failure_domains":[]},"quality":{"source_status":"normal","data_quality_flag":"normal"},"applicability":{"applicability_class":"conditional_machine","evaluation_mode":"machine","evaluation_scope":"circuit_instance","input_semantics":"circuit_design_fact","source_condition_text":"data-processing applications","trigger":{"field":"instance.asset.data_processing_application","op":"is_true"},"approval_gate":null,"exception_condition":{"field":"instance.asset.smaller_neutral_supported_by_analysis_or_field_data","op":"is_true"},"condition_provenance":"source_explicit","normalization_provenance":"editorial_normalization"},"lifecycle":{"primary_phase":"design","primary_phase_label":"Design","applicable_phases":["design"],"phase_links":[{"phase":"design","provenance":"jddg_cross_section_explicit","basis":"Linked to separate JDDG Section 14.8 design evidence/submittal requirements.","phase_label":"Design"}]},"responsibility":{"primary_workflow_owner":"ACT-DESIGNER-AE","primary_workflow_owner_name":"Designer / A-E","actor_assignment_status":"workflow_only","actors":[{"actor_id":"ACT-DESIGNER-AE","actor_name":"Designer / A-E","actor_class":"project_delivery","source_named":true,"relation_type":"workflow_owner","provenance":"editorial_derived","lifecycle_phase":"design","lifecycle_phase_label":"Design","basis":"Workflow owner assigned from lifecycle phase for checklist routing; not a contractual responsibility statement."}]},"verification":{"method":"harmonic_analysis_or_field_data","stage":["design"],"acceptance_criteria":"Neutral >= 200% of phase conductor unless justified by harmonic analysis or field data","evidence_required":["engineering_calculation_or_analysis"],"verification_provenance":"source_implied","evidence_provenance":"source_implied","audit_status":"source_implied_verification","audit_confidence":"high","acceptance_provenance":"source_explicit","evidence_type_ids":["EV-DESIGN-ANALYSIS-FINAL"],"supporting_source_requirements":["JDDG25-14.8.4.3-R01"],"source_support_scope":"design_submittal_or_analysis"},"resolved_evidence":[{"evidence_type_id":"EV-DESIGN-ANALYSIS-FINAL","name":"Final Design Analysis compliance verification","source_requirement_ids":["JDDG25-14.8.4.3-R01"],"stage":["final_design"],"source_scope":"Final Design Analysis should support and verify design compliance with project requirements."}],"supporting_source_requirements":[{"requirement_id":"JDDG25-14.8.4.3-R01","section":"14.8.4.3","title":"DESIGN ANALYSIS","fact":"Final design analysis should support and verify that the design complies with project requirements."}],"references_resolved":[]}